Humanoid robots for safety-critical electrical switching: A perception-informed runtime constraint filter

Songyang Liu, Yu Hou, Yuqing Hu, Shuai Li
In 30 seconds

This preprint describes a safety filter that checks the arm commands sent to a VR-operated Unitree G1. In 12 lab rounds on de-energized switches, the robot completed 10 target operations, with no accidental contact or actuation of the neighboring switch. The filter addresses a practical problem for remote switching on existing panels, where the tool must reach one handle while clearing the hardware next to it.

Research question

Can a humanoid use its onboard camera to keep the operator's chosen switch reachable while filtering live commands that would bring the tool too close to neighboring equipment?

Problem

Operating one of two adjacent switches requires deliberate contact in a confined space. Limited visibility and imprecise or delayed commands can send the tool toward the wrong handle. The switches also sit at different positions relative to the arm each time the humanoid takes up a new stance, so a one-time calibration can become stale.

Previous approach

Substation patrol robots are built mainly for inspection, while device-specific remote actuators often require compatible switchgear or installed hardware. Open-TeleVision and TWIST2 focus on motion tracking and data collection. p-SSA adds live obstacle avoidance to a G1 using geometry sensed by an Apple Vision Pro.

New approach

The Unitree G1 carries a 3D-printed right-wrist tool and takes arm commands from a PICO 4 Ultra through XRoboToolkit. Before operation, its Intel RealSense D435i supplies RGB-D data from manually selected regions. The system fits oriented boxes, leaves the selected switch assembly reachable, and uses a control barrier function quadratic program at a nominal 50 Hz to enforce a 5 cm model clearance around the other assembly and walls. Safe commands pass unchanged. Continued inward commands at the boundary trigger a return to the starting pose, followed by recalibration and explicit operator approval to resume. The filter requires no policy training. A separate MuJoCo version restricts contact to the index fingertip pad and changes allowed motion by task phase.

Results

On one physical G1, one operator ran six rounds at each of two standing positions. Target operation was reported complete in 10/12 rounds. Both failures followed a target switch in round six. There were zero accidental contacts or non-target actuations, and 11/12 rounds triggered an automatic return. The commanded model gap stayed at or above 50.00 mm. Encoder-based minima were 49.04 mm in C1 and 49.55 mm in C2, where the filter modified 8.45% and 26.78% of eligible cycles, respectively. All 180 background QP solves succeeded, averaging about 0.5 ms with a 2.49 ms maximum. Across 36 paired MuJoCo runs on three layouts and three inputs, M3 Complete achieved 9/9 safe completions versus 5/9 for M0 Raw and 6/9 each for M1 Whole target and M2 No direction, gains of four and three runs, respectively. Safe completion required a press and withdrawal without prohibited contact, instability flags or timeout. In four additional map tests, both maps worked after a 30 mm shift. After a 5° rotation, the stale map missed the press and updated geometry restored completion.

Limitations

The hardware evaluation used one robot, one operator, two de-energized general-duty switches and a tool on one arm that limited reach. It had no unfiltered hardware baseline. The hardware filter covers the tool head against a fixed, manually initialized scene model. Part-level contact and phase constraints were tested only in simulation with ground-truth geometry. The longest hardware hold was 61.38 s and required manual return. Holds have no timeout or automatic recovery. Arc effects and electromagnetic compatibility were untested.

Industry impact

Utilities and switchgear automation integrators could consider de-energized pilots in 1 to 3 years if the system proves repeatable on substation-grade cabinets and handles and fits authorized switching and verification procedures. Energized use would also require validated electrical insulation, arc protection, adequate standoff and electromagnetic compatibility.

The full text is not republished here because the paper's license does not allow it. Read the original on arXiv.